| Capacity | Power rating KVA | | 20 | 30 | 40 | 60 | 80 |
| Power rating KW | | 20 | 30 | 40 | 60 | 80 |
| Input | Topology | True Online Double Conversion, IGBT based |
| Rated voltage | 230/400Vac nominal (220/380, 240/415 Selectable) |
| Voltage range | -50% ~ +20% depends on load percentage |
| Input power factor | ≥0.99 |
| THDi | <3% |
| Rated Frequency | 50/60Hz auto sensing |
| Frequency range | 40-72Hz |
| Output | Power factor | 1 |
| Efficiency | Up to 96% in online mode; >99% in ECO mode |
| Output voltage | 230/400Vac nominal (220/380, 240/415 Selectable) |
| Output frequency | 50/60Hz |
| Overload Capacity | 20K-80K models: 102-110% load 60 min, 111-125% load 10 min, 126-150% load 1 min, >150% load 150sec |
| THDv | <2% for Linear load |
| Unbalanced load | 100% |
| Bypass | Internal static switch | Standard |
| Bypass voltage | 400Vac±10% (maximum ±20%) |
| Maintenance bypass switch | Standard |
| Battery | Battery type | 20K-80K models: VRLA/NiCd/Lithium. 20-80K battery kit model: VRLA. 20-80K STD internal battery model: VRLA. |
| Backup time | Varies from battery capacity and load situation. STD internal battery model: 3.5mins @100% load. |
| Battery | Depends on battery configuration. Battery kit: 20-40K up to 2*40Ah/8Ah max; 60-80K up to 4*40Ah/9Ah max. |
| Charger current | 20A | 20A | 30A | 40A | 60A | 80A |
| Battery Voltage | 432VDC default, 320V-607V. STD internal/battery kit: 320V-552V. |
| Communication | Interface | 2x Intelligent-Slot, 1x Emergency Power Off input, 3x Building Alarm inputs, 1x RS-232, 1x USB |
| Com cards (optional) | NMC & CMC cards, relay card, EMP |
| Environment | Running temperature | UPS: 0-40°C; Battery: 25°C |
| Storage | -25 ~ 55°C without battery; -15 ~ 25°C with battery |
| Humidity | 5% ~ 95% |
| Altitude | <1000m without derating |
| Noise level | ≤65dB at 1m @75% Load (ISO7779) |
| Dimension | W*D*H (mm) | 20K/30K/40K: 330*700*525mm | 60K/80K: 330*772*977mm | Battery kit/STD: 20K/30K/40K: 330*780*887mm, 60K/80K: 500*846*1500mm |
| Regulation | Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Performance | IEC/EN 62040-3 |
| Certification | CE |