| Category | Parameter | Cross HD-20K | Cross HD-30K | Cross HD-40K | Cross HD-60K | Cross HD-80K | Cross HD-100K | Cross HD-120K | Cross HD-160K | Cross HD-200K |
|---|---|---|---|---|---|---|---|---|---|---|
| Model | Power rating | 20KVA/20KW | 30KVA/30KW | 40KVA/40KW | 60KVA/60KW | 80KVA/80KW | 100KVA/100KW | 120KVA/120KW | 160KVA/160KW | 200KVA/200KW |
| Input | Wiring | Wiring Three phase+Neutral+Ground | ||||||||
| Mains voltage range | 201 ~ 478Vac (L-L); 116 ~ 276Vac (L-N) | |||||||||
| Bypass voltage range | 338 ~ 458Vac (L-L); 195 ~ 264Vac (L-N) | |||||||||
| Frequency | 50/60Hz | |||||||||
| Frequency range | 42 - 70Hz | |||||||||
| Power factor | ≥0.99 | |||||||||
| THDi | <2% linear load; <5% non-linear load | |||||||||
| Output | Voltage | 230/400Vac default (220/380V,240/415V optional) | ||||||||
| Voltage regulation | <1% @ steady state | |||||||||
| Power factor | 1 | |||||||||
| Overload | 102~110%, 60mins 111~125%, 10mins 126~150%, 1min | |||||||||
| Parallel | Up to 4 units | |||||||||
| Efficiency | Online mode | Up to 96% | ||||||||
| ECO mode | Up to 99% | |||||||||
| Battery | Battery Voltage | 320V~607V (432V default) | ||||||||
| Max charge current | 25A | 38A | 50A | 76A | 100A | 100A | 120A | 160A | 200A | |
| Environment | Ambient temperature | 0-40°C | ||||||||
| Storage temperature | -15 ~ +55°C | |||||||||
| Ambient humidity | 5 - 95% | |||||||||
| Altitude | No derating <1000m | |||||||||
| Physical | Dimension (W*D*H) | 330*668*521mm | 500*850*1230 | 550*850*1600 | ||||||
| Net Weight | 41kg | 45kg | 45kg | 90kg | 90kg | 149kg | 149kg | 245kg | 270kg | |
| Gross weight | 50kg | 55kg | 55kg | 131kg | 131kg | 162kg | 162kg | 270kg | 295kg | |
| Standard | Safety | IEC 62040 | ||||||||